I.10 european standards – Yaskawa 600V User Manual
Page 60

Item
Specification
Protection
Functions
Motor Protection
Electronic thermal overload relay
Momentary Overcurrent
Protection
Drive stops when rated output current exceeds 175%
Overload Protection
Drive stops after 60 s at 110% of rated output current
<2>
Drive stops after 0.5 s at 140% of rated output current
<2>
Overvoltage Protection
600 V class: Stops when DC bus voltage exceeds approx. 1040 V
Undervoltage Protection 600 V class: Stops when DC bus voltage falls below approx. 475 V
Momentary Power Loss
Ride-Thru
Immediately stop after 15 ms or longer power loss
<3>
Continuous operation during power loss shorter than 2 s by speed search function
Heatsink Overheat
Protection
Thermistor
Stall Prevention
Stall Prevention is available during acceleration, deceleration, and during run.
Ground Protection
Electronic circuit protection
<4>
DC Bus Charge LED
Remains lit until DC bus voltage falls below 50 V
Environment
Area of Use
Indoors
Ambient Temperature
-10 °C to +40 °C (14 to 104 °F) IP20/NEMA Type 1 Enclosure
-10 °C to +50 °C (14 to 122 °F) IP00/Open Type Enclosure
Humidity
95% RH or less (no condensation)
Storage Temperature
-20 °C to +70 °C (-4 to +158 °F) (short-term temperature during transportation)
Altitude
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
Vibration/Shock
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
2
(5A0003 to 5A0099)
2.0 m/s
2
(5A0125 to 5A0242)
Standards
• UL508C
• IEC/EN 61800-5-1
• CSA
Protection Design
IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure
<5>
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<2> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
<5> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while
maintaining IP20 conformity. This is applicable to models 5A0003 to 5A0242.
i.10 European Standards
60