I.10 european standards – Yaskawa 600V User Manual

Page 60

background image

Item

Specification

Protection

Functions

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when rated output current exceeds 175%

Overload Protection

Drive stops after 60 s at 110% of rated output current

<2>

Drive stops after 0.5 s at 140% of rated output current

<2>

Overvoltage Protection

600 V class: Stops when DC bus voltage exceeds approx. 1040 V

Undervoltage Protection 600 V class: Stops when DC bus voltage falls below approx. 475 V

Momentary Power Loss

Ride-Thru

Immediately stop after 15 ms or longer power loss

<3>

Continuous operation during power loss shorter than 2 s by speed search function

Heatsink Overheat

Protection

Thermistor

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<4>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

-10 °C to +40 °C (14 to 104 °F) IP20/NEMA Type 1 Enclosure

-10 °C to +50 °C (14 to 122 °F) IP00/Open Type Enclosure

Humidity

95% RH or less (no condensation)

Storage Temperature

-20 °C to +70 °C (-4 to +158 °F) (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Refer to

Altitude Derating on page 58

for details.

Vibration/Shock

10 to 20 Hz: 9.8 m/s

2

20 to 55 Hz: 5.9 m/s

2

(5A0003 to 5A0099)

2.0 m/s

2

(5A0125 to 5A0242)

Standards

• UL508C
• IEC/EN 61800-5-1
• CSA

Protection Design

IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure

<5>

<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<2> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<5> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while

maintaining IP20 conformity. This is applicable to models 5A0003 to 5A0242.

i.10 European Standards

60