Altitude derating, Dimensions, weight, heat loss, Temperature derating – Yaskawa 600V User Manual
Page 58: Dimensions, weight, heat loss notice

u
Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in
installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable
drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.
n
Parameter Settings
No.
Name
Description
Range
Def.
L8-12
Ambient
Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is installed
in an environment that exceeds its ambient temperature rating.
40 to 60
30 °C
L8-35
Installation Method
Selection
0: IP00/Open-Chassis Enclosure
2: IP20/NEMA Type 1 Enclosure
3: External Heatsink Installation
0, 2, 3
2
IP00/Open-Chassis Enclosure
Drive operation between -10 °C and +50 °C (14 and 122 °F) allows 100% continuous current without derating.
IP20/NEMA Type 1 Enclosure
Drive operation between -10 °C and +40 °C (14 and 104 °F) allows 100% continuous current without derating. Operation
between 40 °C and 50 °C (104 and 122 °F) requires output current derating.
Note:
The temperature derating remains unchanged when removing the top protective cover and the bottom conduit bracket to change an IP20/
NEMA Type 1 enclosure drive to an IP00/Open-Type enclosure drive (derating required for temperatures over 40 °C [104 °F]).
External Heatsink Installation
Drive operation between -10 °C and +40 °C (14 and 104 °F) allows 100% continuous current without derating. Operation
between 40 °C and 50 °C (104 and 122 °F) requires output current derating.
40
°C
100%
60%
-10
°C
0%
50
°C
80%
IP20/NEMA Type 1
IP00/Open-Type
External Heatsink
Figure i.20 Ambient Temperature and Installation Method Derating
u
Altitude Derating
The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive
rated voltage and the rated output current must be derated for 0.2% per 100 m.
u
Dimensions, Weight, Heat Loss
NOTICE
Refer to the Mechanical Installation Chapter and the Specifications Chapter of the Z1000 User Manual (600 V models)
TOEPYAIZ1U03 which can be found on the CD-ROM packaged with the product.
i.10 European Standards
58