Yaskawa 600V User Manual

Page 47

background image

HOA Keypad

ALM FLT

Cause

Possible Solution

Drive Disabled

dnE

O

“Drive Enable” is set to a multi-function contact

input (H1-oo = 6A) and that signal was

switched off.

Check the operation sequence.

Option External Fault

EF0

O

O

An external fault was received from the PLC and

F6-03 is set to a value other than 3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

External Fault

EF1 to EF7

O

O

An external device tripped an alarm function

Remove the cause of the external fault and reset the fault.

Multi-function contact input setting is incorrect

• Check for unused terminals set for H1-oo = 20 to 2B

(External Fault).

• Change the terminal settings.

EEPROM Write Error

Err

O

Noise has corrupted data while writing to the

EEPROM

• Press “ENTER” on the HOA keypad.
• Correct the parameter setting.
• Cycle power to the drive.
• If the problem continues, replace the control board or the

entire drive. Contact Yaskawa or a Yaskawa representative

for instructions on replacing the control board.

Internal Fan Fault

FAn

O

O

Internal cooling fan has malfunctioned

• Cycle power to the drive.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor

U4-03, and verify the cumulative operation time of the fan

maintenance timer with U4-04.

• If the cooling fan has exceeded its expected performance life

or is damaged in any other way, replace the fan.

Excessive PID

Feedback

FbH

O

O

Parameters are set inappropriately

Check b5-36 and b5-37 settings.

Incorrect PID feedback wiring

Correct the wiring.

PID Feedback Loss

FbL

O

O

Parameters are set inappropriately

Check b5-13 and b5-14 settings.

Incorrect PID feedback wiring

Correct the wiring.

Ground Fault

GF

O

Motor insulation is damaged

• Check the insulation resistance of the motor.
• Replace the motor.

A damaged motor cable is creating a short circuit

• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground

terminal .

• Replace the cable.

Excessive leakage current at the drive output

• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.

Output Phase Loss

LF

O

The output cable is disconnected

• Check for wiring errors and properly connect the output

cable.

• Correct the wiring.

The motor winding is damaged

• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.

Output Current

Imbalance

LF2

O

Phase loss has occurred on the output side of the

drive

• Check for faulty wiring or poor connections on the output

side of the drive.

• Correct the wiring.

Motor impedance or motor phases are uneven

• Measure the line-to-line resistance for each motor phase.

Ensure all values match.

• Replace the motor.

Cooling Fan

Maintenance Time

LT-1

O

The cooling fan has reached 90% of its expected

performance life.

Replace the cooling fan and set o4-03 to 0 to reset the

Maintenance Monitor.

i.8 Troubleshooting

YASKAWA ELECTRIC TOEP YAIZ1U 02A YASKAWA AC Drive – Z1000 Safety Precautions

47