Parameter Table

This parameter table shows the most important parameters. Default settings are in bold type. Refer to the Programming Manual

for a complete list of parameters.

No.

Name

Description

A1-00

Language Selection

0: English

1: Japanese

3: French

5: Spanish

6: Portuguese

A1-02

Control Method

Selection

0: V/f Control

5: Open Loop Vector Control for PM

A1-03

Initialize Parameters

0: No initialization

1110: User Initialize (parameter values

must be stored using parameter o2-03)

2220: 2-Wire Initialization

3330: 3-Wire Initialization

3410: HVAC Initialization

3420: OEM Bypass Initialization

A1-04

Password

When the value set into A1-04 does not

match the value set into A1-05, parameters

A1-01 through A1-03, A1-06, and A2-01

through A2-33 cannot be changed.

A1-05

Password Setting

A1-06

Application Preset

0: Standard

1: Fan

2: Fan with PI Control

3: Return Fan with PI Control

4: Cooling Tower Fan

5: Cooling Tower Fan with PI Control

6: Pump (Secondary)

7: Pump with PI Control

A2-01 to

A2-32

User Parameters 1 to 32

Recently edited parameters are listed here.

The user can also select parameters to

appear here for quicker access.

b1-01

Frequency Reference

Selection for AUTO

Mode

0: HOA keypad

1: Terminals (Analog Input Terminals)

2: Serial communications (APOGEE FLN,

BACnet, MEMOBUS/Modbus, or Metasys

N2)

3: Option card

b1-02

Run Command

Selection for AUTO

Mode

1: Control Circuit Terminal

2: Serial communications (APOGEE

FLN, BACnet, MEMOBUS/Modbus, or

Metasys N2)

3: Option card

b1-03

Stopping Method

Selection

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

b1-04

Reverse Operation

Selection

0: Reverse enabled

1: Reverse disabled

b1-14

Phase Order Selection

0: Standard

1: Switch phase order (reverses the

direction of the motor)

b1-17

Run Command at

Power Up

0: Disregarded

A new Run command must be issued after

power up.

1: Allowed

Motor will start immediately after power up

if a Run command is already enabled.

b2-01

DC Injection Braking

Start Frequency

Sets the frequency at which DC Injection

Braking starts when “Ramp to stop” (b1-03

= 0) is selected.

b2-02

DC Injection Braking

Current

Sets the DC Injection Braking current as a

percentage of the drive rated current.

b2-03

DC Injection Braking

Time at Start

Sets DC Injection Braking time at start.

Disabled when set to 0.00 seconds.

b2-04

DC Injection Braking

Time at Stop

Sets DC Injection Braking time at stop.

No.

Name

Description

b2-09

Motor Pre-Heat

Current 2

Determines the percentage of motor rated

output current used for the motor pre-heat

function.

b3-01

Speed Search Selection

at Start

0: Disabled

1: Enabled

Note: Default setting is dependent upon

parameter A1-02, Control Method

Selection.

b3-02

Speed Search

Deactivation Current

Sets the current level at which the speed is

assumed to be detected and Speed Search is

ended. Set as a percentage of the drive rated

current.

b3-03

Speed Search

Deceleration Time

Sets output frequency reduction time during

Speed Search.

b3-04

V/f Gain during Speed

Search

Determines how much to lower the V/f ratio

during Speed Search.

Output voltage during Speed Search equals

the V/f setting multiplied by b3-04.

b3-05

Speed Search Delay

Time

When using an external contactor on the

output side, b3-05 delays executing Speed

Search after a momentary power loss to

allow time for the contactor to close.

b3-06

Output Current 1

during Speed Search

Sets the current injected to the motor at the

beginning of Speed Estimation Speed

Search. Set as a coefficient for the motor

rated current.

b3-10

Speed Search

Detection

Compensation Gain

Sets the gain which is applied to the speed

detected by Speed Estimation Speed Search

before the motor is reaccelerated. Increase

this setting if ov occurs when performing

Speed Search after a relatively long period

of baseblock.

b3-14

Bi-Directional Speed

Search Selection

0: Disabled (uses the direction of the

frequency reference)

1: Enabled (drive detects which way the

motor is rotating)

Note: Default setting is dependent upon

parameter A1-02, Control Method

Selection.

b3-17

Speed Search Restart

Current Level

Sets the Speed Search restart current level

as a percentage of the drive rated current.

b3-18

Speed Search Restart

Detection Time

Sets the time to detect Speed Search restart.

b3-19

Number of Speed

Search Restarts

Sets the number of times the drive can

attempt to restart when performing Speed

Search.

b3-24

Speed Search Method

Selection

0: Current Detection

1: Speed Estimation

b3-25

Speed Search Wait

Time

Sets the time the drive must wait between

each Speed Search restart attempt.

b3-27

Start Speed Search

Select

0: Triggered when a Run command is

issued. (normal).

1: Triggered when an external baseblock is

released.

b5-01

PI Function Setting

0: Disabled

1: Enabled (PI output becomes output

frequency reference)

3: Enabled (PI output added to frequency

reference)

b5-02

Proportional Gain

Setting (P)

Sets the proportional gain of the PI

controller.

b5-03

Integral Time Setting

(I)

Sets the integral time for the PI controller.