beautypg.com

European standards, Ce low voltage directive compliance, Drive derating data – Yaskawa 600V User Manual

Page 57: I.10 european standards

background image

i.10 European Standards

Figure i.19 CE Mark

The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business

and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics

manufacturers, and the EMC guidelines for controlling noise.
This drive is in conformance with the Low Voltage Directive.
Low Voltage Directive: 2006/95/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying

the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE

standards. After setting up the device, verify that conditions meet European standards.

u

CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage

Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other

devices:

n

Area of Use

Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.

n

Factory Recommended Branch Circuit Protection

NOTICE

Refer to the Z1000 User Manual (600 V models) TOEPYAIZ1U03 on the CD-ROM No. TOECC71061615 packaged with
the product; Chapter- Standards Compliance, Section-European Standards , for more information on Factory
Recommended Branch Circuit Protection
for CE Compliance.

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded

systems, contact your Yaskawa representative for instructions.

n

Guarding Against Harmful Materials

When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive

from above or below.

u

Drive Derating Data

n

Rated Current Depending on Carrier Frequency

Increasing the carrier frequency above 2 kHz will reduce the rated output current of the drive.

NOTICE

Refer to the Z1000 User Manual (600 V models) TOEPYAIZ1U03 – Drive Derating Data section to assist in model selection
and adjustment when the application requires changing the drive carrier frequency from factory defaults.

i.10 European Standards

YASKAWA ELECTRIC TOEP YAIZ1U 02A YASKAWA AC Drive – Z1000 Safety Precautions

57