I.4 standard connection diagram – Yaskawa 600V User Manual
Page 22

Drive Model
Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0125
R/L1, S/L2, T/L3
70
(2/0)
35 to 150
(1 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
70
(2/0)
35 to 150
(1 to 300)
⊖, ⊕1
–
70
(2/0 to 3/0)
⊕3
–
35 to 50
(1 to 1/0)
35
(3)
35 to 150
(3 to 300)
5A0145
R/L1, S/L2, T/L3
95
(3/0)
95 to 150
(2/0 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
95
(3/0)
95 to 150
(2/0 to 300)
⊖, ⊕1
–
70 to 95
(3/0 to 4/0)
⊕3
–
70 to 95
(1/0 to 2/0)
35
(3)
35 to 150
(3 to 300)
5A0192
R/L1, S/L2, T/L3
185
(300)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
150
(250)
95 to 300
(2/0 to 600)
⊖, ⊕1
–
95 to 185
(2/0 to 400)
⊕3
–
95 to 120
(2/0 to 250)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3
240
(400)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185
(350)
95 to 300
(2/0 to 600)
⊖, ⊕1
–
95 to 240
(2/0 to 500)
⊕3
–
150
(250 to 300)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
Note:
When connecting peripheral devices or options to terminals
⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
i.4 Standard Connection Diagram
22
YASKAWA ELECTRIC TOEP YAIZ1U 02A YASKAWA AC Drive – Z1000 Safety Precautions