UL and CSA Standards

u

UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and

evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

Figure i.16 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described

below must be met to maintain compliance when using this drive in combination with other equipment:

n

Installation Area

Do not install the drive to an area greater than pollution degree 2 (UL standard).

n

Ambient Temperature

IP20/NEMA Type 1 Enclosure: -10 to +40 °C
IP00 Open Type Enclosure: -10 to +50 °C

n

Main Circuit Terminal Wiring

Wire Gauges and Tightening Torques

Refer to Main Circuit Wire Gauges and Tightening Torque on page 19

for details.

Closed-Loop Crimp Terminal Recommendations

Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed

closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 5A0041 to

5A0242. Use only the tools recommended by the terminal manufacturer for crimping.

Refer to Closed-Loop Crimp Terminal

Recommendations on page 23

for closed-loop crimp terminal recommendations.

Note:

The mark indicates the terminals for protective ground connection as defined in IEC/EN 60417-5019.

Grounding impedance: 600 V: 10 Ω or less

.

Factory Recommended Branch Circuit Protection for UL Compliance

NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.

Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral

devices if the cause cannot be identified.

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in

Table i.20

.

Table i.20 Factory Recommended Drive Branch Circuit Protection

Drive Model

Nominal

Output Power

HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

Time Delay Fuse

Rating Amps

<2>

Non-time Delay

Fuse Rating

Amps

<3>

Bussmann Semi-

conductor Fuse

Rating (Fuse

Ampere)

<4>

600 V Class

5A0003

2

3.6

15

6.25

10

FWP-50B (50)

5A0004

3

5.1

15

8

15

FWP-50B (50)

5A0006

5

8.3

15

12

20

FWP-60B (60)

5A0009

7.5

12

20

20

35

FWP-60B (60)

5A0011

10

16

30

25

45

FWP-70B (70)