beautypg.com

Control circuit output terminals, Serial communication terminals – Yaskawa 600V User Manual

Page 26

background image

u

Control Circuit Output Terminals

Table i.7

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.

Table i.7 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Fault Relay

Output

MA

N.O. output (Fault)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

MB

N.C. output (Fault)

MC

Fault output common

Multi-Function
Digital Output

<1>

M1

Multi-function digital output (During run)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function digital output (Zero speed)

M4
M5

Multi-function digital output (Speed Agree 1)

M6

Monitor Output

FM

Analog monitor output 1 (Output frequency)

0 to 10 V / 0 to 100%

4 to 20 mA / 0 to 100%

Voltage or current output must be selected by Jumper S5 and H4-07

for FM and H4-08 for AM.

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

External Power

Supply

+P

External Power Supply

24 V (Max. 150 mA)

<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching

life is estimated at 200,000 times (assumes 1 A, resistive load).

Connect a suppression diode as shown in

Figure i.8

when driving a reactive load such as a relay coil. Ensure the diode rating

is greater than the circuit voltage.

A

B

C

D

A – External power, 48 V max.
B – Suppression diode

C – Coil
D – 50 mA or less

Figure i.8 Connecting a Suppression Diode

n

Serial Communication Terminals

Table i.8 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

Serial Communication

(APOGEE FLN,

BACnet, MEMOBUS/

Modbus, or Metasys
N2)

<1>

R+

Communications input (+)

APOGEE FLN, BACnet, MEMOBUS/

Modbus, or Metasys N2 communication: Use

an RS-422 or RS-485 cable to connect the

drive.

• APOGEE FLN

Comm. RS-422/

RS-485, 4.8 kbps

• BACnet Comm.

RS-485, max. 76.8

kbps

• MEMOBUS/

Modbus Comm.

RS-422/RS-485,

max. 115.2 kbps

• Metasys N2 Comm.

RS-422/RS-485, 9.6

kbps

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Communications ground

0 V

FE

Option card ground

<1> Enable the termination resistor in the last drive in an APOGEE FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 network by setting DIP switch

S2 to the ON position.

i.4 Standard Connection Diagram

26

YASKAWA ELECTRIC TOEP YAIZ1U 02A YASKAWA AC Drive – Z1000 Safety Precautions