HOA Keypad

Cause

Possible Solution

Er-09

Acceleration Error

The motor did not accelerate for the specified acceleration time.

• Increase the acceleration time (C1-01).
• Disconnect the machine from the motor if possible.

The load was too high during Rotational Auto-Tuning.

• Disconnect the motor from machine and restart Auto-Tuning. If

motor and load cannot be uncoupled make sure the load is lower

than 30%.

• If a mechanical brake is installed, make sure it is fully lifted

during tuning.

Er-12

Current Detection Error

One of the motor phases is missing: (U/T1, V/T2, W/T3).

Check motor wiring and correct any problems.

The current exceeded the current rating of the drive.

• Check motor wiring for a short between motor lines.
• Close any magnetic contactors used between motors.
• Replace the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or your nearest

sales representative.

The current is too low.

u

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different

ways to restart the drive.

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the drive, and

reset the fault

Press

on the HOA keypad.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

-DRIVE-

U1- 01=60.00Hz

----------------

U1- 02=60.00Hz

JOG FWD FWD/REV

-Rdy-

ALM

DIGITAL OPERATOR JVOP-183

HAND

Freq Ref (OPR)

Resetting via Fault Reset Digital Input S4

Close then open the fault signal digital input via

terminal S4. S4 is set for “Fault Reset” as default

(H1-04 = 14).

Fault Reset Switch

Drive

S4 Fault Reset Digital Input

SC Digital Input Common

Turn off the main power supply if the above methods do not reset the fault. Reapply power after the

HOA keypad display has turned off.

When an “SC” error occurs, contact Yaskawa or a Yaskawa agent before cycling the power to the drive.

ON

OFF

2

1

Note:

If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear

a fault situation.

i.8 Troubleshooting

52