No.

Name

Description

H3-03

Terminal A1 Gain

Setting

Sets the level of the input value selected in

H3-02 when 10 V is input at terminal A1.

H3-04

Terminal A1 Bias

Setting

Sets the level of the input value selected in

H3-02 when 0 V is input at terminal A1.

H3-09

Terminal A2 Signal

Level Selection

0: 0 to 10 V with zero limit

1: 0 to 10 V without zero limit

2: 4 to 20 mA

3: 0 to 20 mA

Note: Use Jumper S1 to set input terminal

A2 for a current or voltage input signal.

H3-10

Terminal A2 Function

Selection

Sets the function of terminal A2.

H3-11

Terminal A2 Gain

Setting

Sets the level of the input value selected in

H3-10 when 10 V (20 mA) is input at

terminal A2.

H3-12

Terminal A2 Bias

Setting

Sets the level of the input value selected in

H3-10 when 0 V (0 or 4 mA) is input at

terminal A2.

H5-01

Drive Node Address

Selects drive station slave number (address)

for MEMOBUS/Modbus terminals R+, R-,

S+, S-. Cycle power for the setting to take

effect.

H5-02

Communication Speed

Selection

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Cycle power for the setting to take effect.

H5-03

Communication Parity

Selection

0: No parity

1: Even parity

2: Odd parity

Cycle power for the setting to take effect.

H5-04

Stopping Method After

Communication Error

(CE)

0: Ramp to stop

1: Coast to stop

2: Fast Stop

3: Alarm only

4: Run at d1-04

H5-05

Communication Fault

Detection Selection

0: Disabled

1: Enabled. If communication is lost for

more than two seconds, a CE fault will

occur.

H5-06

Drive Transmit Wait

Time

Set the wait time between receiving and

sending data.

H5-07

RTS Control Selection

0: Disabled. RTS is always on.

1: Enabled. RTS turns on only when

sending.

H5-08

Communication

Protocol Selection

0: MEMOBUS/Modbus

1: N2 (Metasys)

2: P1 (APOGEE FLN)

3: BACnet

H5-09

CE Detection Time

Sets the time required to detect a

communications error.

Adjustment may be needed when

networking several drives.

H5-10

Unit Selection for

MEMOBUS/Modbus

Register 0025H

0: 0.1 V units

1: 1 V units

H5-11

Communications

ENTER Function

Selection

0: Drive requires an Enter command

before accepting any changes to

parameter settings.

1: Parameter changes are activated

immediately without the Enter command.

H5-12

Run Command

Method Selection

0: FWD/Stop, REV/Stop

1: Run/Stop, FWD/REV

No.

Name

Description

L2-01

Momentary Power

Loss Operation

Selection

0: Disabled.

Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02.

Uv1 will be detected if power loss is longer

than L2-02.

2: Recover as long as CPU has power.

Uv1 is not detected.

L2-02

Momentary Power

Loss Ride-Thru Time

Sets the Power Loss Ride-Thru time.

Enabled only when L2-01 = 1 or 3.

L2-03

Momentary Power

Loss Minimum

Baseblock Time

Sets the minimum wait time for residual

motor voltage decay before the drive output

reenergizes after performing Power Loss

Ride-Thru.

Increasing the time set to L2-03 may help if

overcurrent or overvoltage occur during

Speed Search or during DC Injection

Braking.

Note: Default setting is dependent upon

parameter o2-04, Drive Model Selection.

L4-05

Frequency Reference

Loss Detection

Selection

0: Stop. Drive stops when the frequency

reference is lost.

1: Run. Drive runs at a reduced speed

when the frequency reference is lost.

L4-06

Frequency Reference

at Reference Loss

Sets the percentage of the frequency

reference that the drive should run with

when the frequency reference is lost.

L5-01

Number of Auto

Restart Attempts

Sets the number of times the drive may

attempt to restart after the following faults

occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,

STo, Uv1.

L5-02

Auto Restart Fault

Output Operation

Selection

0: Fault output not active.

1: Fault output active during restart attempt.

L5-03

Time to Continue

Making Fault Restarts

Enabled only when L5-05 is set to 0. Causes

a fault if a fault restart cannot occur after the

set time passes.

L5-04

Fault Reset Interval

Time

Sets the amount of time to wait between

performing fault restarts.

L5-05

Fault Reset Operation

Selection

0: Continuously attempt to restart while

incrementing restart counter only at a

successful restart.

1: Attempt to restart with the interval

time set in L5-04 and increment the

restart counter with each attempt.

L6-01

Torque Detection

Selection 1

0: Disabled

1: oL3 detection only active during speed

agree, operation continues after detection

2: oL3 detection always active during run,

operation continues after detection

3: oL3 detection only active during speed

agree, output shuts down on an oL3 fault

4: oL3 detection always active during run,

output shuts down on an oL3 fault

5: UL3 detection only active during speed

agree, operation continues after detection

6: UL3 detection always active during run,

operation continues after detection

7: UL3 detection only active during speed

agree, output shuts down on an oL3 fault

8: UL3 detection always active during run,

output shuts down on an oL3 fault

9: UL6 at speed agree (alarm)

10: UL6 at run (alarm)

11: UL6 at speed agree (fault)

12: UL6 at run (fault)

L6-02

Torque Detection

Level 1

Sets the overtorque and undertorque

detection level.

L6-03

Torque Detection Time

1

Sets the time an overtorque or undertorque

condition must exist to trigger torque

detection 1.

L6-13

Motor Underload

Protection Selection

0: Overtorque/undertorque detection

enabled

1: Base frequency motor load enabled

i.7 Parameter Table

YASKAWA ELECTRIC TOEP YAIZ1U 02A YASKAWA AC Drive – Z1000 Safety Precautions

41