beautypg.com

Auto-tuning errors – Yaskawa 600V User Manual

Page 51

background image

HOA Keypad

Cause

Possible Solution

oPE09

The following simultaneous contradictory settings have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function Operation Level)
• The stopping method is set to either DC Injection Braking or coast

to stop with a timer (b1-03 = 2 or 3).

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop

(b1-03 = 0 or 1).

oPE10

V/f pattern setting error.

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.

oPE11

The following simultaneous contradictory settings have occurred:

C6-05 > 6 and C6-04 > C6-03 (carrier frequency lower limit is

greater than the upper limit).

If C6-05 ≤ 6, the drive operates at C6-03.

Correct the parameter settings.

The upper and lower limits between C6-02 and C6-05 are

contradictory.

oPE16

The following contradictory settings are true:

A1-02 = 0, S1-01 =1, and b8-01 = 1

Correct the parameter settings.

oPE27

If digital inputs A4, A5, or A7 or digital outputs A4 or A5 are

programmed, then all must be programmed

Correct the parameter settings.

oPE28

• S2-01 > S2-02
• S2-06 > S2-07
• S2-11 > S2-12
• S2-16 > S2-17

Correct the parameter settings.

u

Auto-Tuning Errors

HOA Keypad

Cause

Possible Solution

End3

Rated current alarm

The correct current rating printed on the motor nameplate was not

entered into T1-04.

• Check the setting of parameter T1-04.
• Check the motor data and repeat Auto-Tuning.

End4

Adjusted Slip Calculation Error

The calculated slip is outside the allowable range.

• Make sure the data entered for Auto-Tuning is correct.
• If possible, perform Rotational Auto-Tuning. If not possible,

perform Stationary Auto-Tuning 2.

End5

Resistance Tuning Error

The calculated slip is outside the allowable range.

• Double-check the data entered for the Auto-Tuning process.
• Check the motor and motor cable connection for faults.

End7

No-Load Current Alarm

The entered no-load current value was outside the allowable range. Check and correct faulty motor wiring.
Auto-Tuning results were less than 5% of the motor rated current. Double-check the data entered for the Auto-Tuning process.

Er-01

Motor data error

Motor data or data entered during Auto-Tuning was incorrect.

• Check that the motor data entered to T1 parameters matches

motor nameplate input before Auto-Tuning.

• Restart Auto-Tuning and enter the correct information.

Motor output power and motor-rated current settings (T1-02 and

T1-04) do not match.

• Check the drive and motor capacities.
• Correct the settings of parameters T1-02 and T1-04.

Motor rated current and detected no-load current are inconsistent.

• Check the motor rated current and no-load current.
• Correct the settings of parameters T1-04 and E2-03.

Er-02

Minor Fault

An alarm was triggered during Auto-Tuning.

Exit the Auto-Tuning menu, check the alarm code, remove the

alarm cause, and repeat Auto-Tuning.

Er-03

Auto-Tuning canceled by pressing STOP button.

Auto-Tuning did not complete properly. Restart Auto-Tuning.

Er-04

Line-to-Line Resistance Error

Motor data entered during Auto-Tuning was incorrect.

• Make sure the data entered to the T1 parameters match the

information written on the motor nameplate.

• Restart Auto-Tuning and enter the correct information.

Faulty motor cable or cable connection.

Check and correct faulty motor wiring.

Er-05

Er-08

No-Load Current Error/Rated Slip Error

Motor data entered during Auto-Tuning was incorrect.

Results from Auto-Tuning are outside the parameter setting range

or the tuning process took too long.

• Make sure the data entered to the T1 parameters match the

information written on the motor nameplate.

• Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the parameter setting range

or the tuning process took too long.

• Check and correct faulty motor wiring.
• Perform Rotational Auto-Tuning.

i.8 Troubleshooting

YASKAWA ELECTRIC TOEP YAIZ1U 02A YASKAWA AC Drive – Z1000 Safety Precautions

51