Ground Wiring

Follow the precautions below when wiring the ground for one drive or a series of drives.

WARNING! Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local safety

regulations. Failure to comply may result in death or serious injury.

WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize

the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could

result in death or serious injury.

WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (600 V class: ground to 10 Ω or less). Improper equipment

grounding could result in death or serious injury by contacting ungrounded electrical equipment.

NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper

equipment grounding could result in drive or equipment malfunction due to electrical interference.

NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in

abnormal operation of drive or equipment.

Refer to

Figure i.6

when using multiple drives. Do not loop the ground wire.

Figure i.6 Multiple Drive Wiring

u

Control Circuit Connections

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S7), multi-function digital outputs

(M1 to M4), multi-function analog inputs (A1 to A3), and multi-function analog monitor output (FM, AM). The default setting

is listed next to each terminal in

Figure i.5

on page

17

.

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with

untested control circuits could result in death or serious injury.

WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter

A1-06 may change the I/O terminal function automatically from the factory setting. Failure to comply may result in death or serious injury.

i.4 Standard Connection Diagram

24