11 appendix 3 terminal size and wire gauge – Yaskawa GPD515/G5 User Manual
Page 73

11 Appendix 3 Terminal Size and Wire Gauge
YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide
73
A1000
5A0077
R/L1, S/L2, T/L3
M10
18 to 23
(159 to 204)
5.5 to 105
(10 to 4/0)
30
(3)
U/T1, V/T2, W/T3
M10
18 to 23
(159 to 204)
5.5 to 105
(10 to 4/0)
30
(3)
-, +1, +2
M10
18 to 23
(159 to 204)
30 to 105
(3 to 4/0)
─
B1, B2
M10
18 to 23
(159 to 204)
14 to 105
(6 to 4/0)
─
M10
18 to 23
(159 to 204)
20
(4)
20
(4)
G5
5055
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3, -, +3
M8
─
30 to 50
(2 to 1/0)
─
Pressure
Lug
─
22 to 30
(6 to 2)
─
r,
M4
─
2 to 5.5
(14 to 10)
─
A1000
5A0099
R/L1, S/L2, T/L3
M10
18 to 23
(159 to 204)
5.5 to 105
(10 to 4/0)
50
(1/0)
U/T1, V/T2, W/T3
M10
18 to 23
(159 to 204)
5.5 to 105
(10 to 4/0)
50
(1)
-, +1, +2
M10
18 to 23
(159 to 204)
40 to 105
(2 to 4/0)
─
B1, B2
M10
18 to 23
(159 to 204)
20 to 105
(4 to 4/0)
─
M10
18 to 23
(159 to 204)
20
(4)
20
(4)
G5
5075
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3, -, +3
M8
─
50 to 60
(2/0 to 1//0)
─
Pressure
Lug
─
22 to 30
(6 to 2)
─
r,
M4
─
2 to 5.5
(14 to 10)
─
A1000
5A0125
R/L1, S/L2, T/L3
─
─
─
─
U/T1, V/T2, W/T3
─
─
─
─
-, +1, +2
─
─
─
─
B1, B2
─
─
─
─
─
─
─
─
G5
5090
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3, -, +3
M10
─
80 to 150
(3/0 to 300)
─
Pressure
Lug
─
22 to 60
(4 to 2/0)
─
r,
M4
─
2 to 5.5
(14 to 10)
─
A1000
5A0145
R/L1, S/L2, T/L3
─
─
─
─
U/T1, V/T2, W/T3
─
─
─
─
-, +1, +2
─
─
─
─
B1, B2
─
─
─
─
─
─
─
─
G5
5110
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3, -, +3
M12
─
150 to 200
(300 to 400)
─
Pressure
Lug
─
22 to 60
(4 to 2/0)
─
r,
M4
─
2 to 5.5
(14 to 10)
─
Series
Model
Terminal Signal
Terminal
Screw
Tightening Torque
N ・ m (lb.in.)
Possible Gauges
mm
2
(AWG/kcmil)
Recommended
Gauge mm
2
(AWG/
kcmil)