10 Appendix 2 Parameter Cross Reference

58

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

Display Setting/
Selection

Frequecny units of
reference setting and
monitor

o1-03

0

o1-03

0

o1-03

o1-03

0: 0.01 Hz units

0: 0.01 Hz units

1: 0.01% units

1: 0.01% units

2 to 39: r/min units

2: r/min units

40 to 39999: User-set units

3: User-set units
o1-10

01-11

1 to 60000

0 to 3

o1-10: Determines how the units for the frequency reference.
o1-11: Sets the decimal point for the frequency reference display.
Ex. : For a max output frequency of 200.0, set the following:

Setting value :
o1-03 = 12000

Setting value: o1-03=3
: o1-10=2000
: o1-11=1

1 2 0 0 0
│ └ Max value, excluding decimal point
→ o1-10=“2000”
└── digits displayed to the right of the decimal
→ o1-11= 1

Frequency units of
constant setting

o1-04

0

o1-04

0

o1-04

o1-04

0: Hz units

0: Hz units

1: r/min units

1: r/min units

Constant No. display
selection

o1-05

0

o1-05

0: Normally display

No need to set

1: Display MEMOBUS reg.

Not available in A1000

Multi-Function
Selection

LOCAL/REMOTE
Key Enable/Disable

o2-01

1

o2-01

1

o2-01

o2-01

0: Disabled

0: Disabled

1: Enabled

1: Enabled

STOP Key During
Control Circuit
Terminal Operation

o2-02

1

o2-02

1

o2-02

o2-02

0: Disabled

0: Disabled

1: Enabled

1: Enabled

User Constant Initial
Value

o2-03

0

o2-03

0

o2-03

o2-03

0: No change

0: No change

1: Save values

1: Save values

2: Clear memory

2: Clear memory

kVA Selection

o2-04

*

o2-04

*

*Do not change this setting. Depends on drive capacity.

Frequency Reference
Setting Method
Selection

o2-05

0

o2-05

0

o2-05

o2-05

0: ENTER required

0: ENTER required

1: ENTER key not required

1: ENTER key not required

Operation Selection
when Digital Operator
is Disconnected

o2-06

1

o2-06

1

o2-06

o2-06

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Cumulative Operation
Time Setting

o2-07

0H

o4-01

0 H

Cumulative Operation
Time Selection

o2-08

0

o4-02

0

o2-08

o4-02

0: Whenever the power is on

0: Whenever the power is on

1: During run only

1: During run only

Initialize Mode
Selection

o2-09

1*

o2-09

*

*Do not change this setting.

Parameter Name

G5

A1000

Comments (Gray shading indicates default settings)

No.

Default

No.

Default

G5

A1000