beautypg.com

10 appendix 2 parameter cross reference – Yaskawa GPD515/G5 User Manual

Page 49

background image

10 Appendix 2 Parameter Cross Reference

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

49

Multi-Function Input

Multi-function input 1
(terminal 3) (S3 in
A1000)

H1-01

24

H1-03

24

C: Multi-func analog input
selection

C: Multi-func analog input
selection

D: Speed control disabled
(V/f with PG)

D: Speed control disabled
(V/f with PG)

E: Speed control integral reset

E: Speed control integral reset

F: Not used

F: Through-mode

10: Up comamnd

10: Up command

11: Down command

11: Down command

12: FWD jog

12: FWD jog

13: REV jog

13: REV jog

Multi-function input 2
(terminal 4) (S4 in
A1000)

H1-02

14

H1-04

14

14: Fault Reset

14: Fault Reset

15: Emergency Stop (N.O.)

15: Fast Stop (N.O.)

16: Motor switch command

16: Motor switch command

17: Fast Stop (N.O.)

17: Fast Stop (N.O.)

18: Timer function input

18: Timer function input

19: PID control cancel

19: PID control cancel

1A: Accel/decel time selection
2

1A: Accel/decel time selection
2

1B: Write allowed

1B: Write allowed

1C: +Speed Command

44: Off-set frequency 1 (added)

1D: -Speed Command

45: Off-set frequency 2 (added)

1E: Analog freq ref sample hold 1E: Analog freq ref sample/hold

1F: Freq ref terminal 13/14
selection

Set H1-oo=3, H3-02=0,
H3-06=3, H3-10=2, then switch
the terminal assigned by the H1
parameter.*

* If just using the terminal 13/14 switch, then set the following:

Multi-function input 3
(terminal 5)
(S5 in A1000)

H1-03

3 (0)

H1-05

3 (0)

Terminal

Terminal 13/
14 Switch
H1-XX=1F

Terminal

Multi-Speed
Reference 1
H1-00=3

13

OFF

A1

OFF

14

ON

A2

ON

20: External fault (N.O.,
Always detected, Ramp to stop)

20: External fault (N.O.,
Always detected, Ramp to stop)

21: External fault (N.C.,
Always detected, Ramp to stop)

21: External fault (N.C.,
Always detected, Ramp to stop)

22: External fault (N.O.,
Detected during run, Ramp to
stop)

22: External fault (N.O.,
Detected during run, Ramp to
stop)

23: External fault (N.C.,
Detected during run, Ramp to
stop)

23: External fault (N.C.,
Detected during run, Ramp to
stop)

24: External fault (N.O.,
Always detected, Coast to stop)

24: External fault (N.O.,
Always detected, Coast to stop)

25: External fault (N.C.,
Always detected, Coast to stop)

25: External fault (N.C.,
Always detected, Coast to stop)

26: External fault (N.O.,
Detected during run, Coast to
stop)

26: External fault (N.O.,
Detected during run, Coast to
stop)

27: External fault (N.C.,
Detected during run, Coast to
stop)

27: External fault (N.C.,
Detected during run, Coast to
stop)

28: External Fault (N.O.,
always detected, Fast Stop)

28: External Fault (N.O.,
always detected, Fast Stop)

29: External fault (N.C.,
always detected, Fast Stop)

29: External fault (N.C.,
always detected, Fast Stop)

Parameter Name

G5

A1000

Comments (Gray shading indicates default settings)

No.

Default

No.

Default

G5

A1000