beautypg.com

10 appendix 2 parameter cross reference – Yaskawa GPD515/G5 User Manual

Page 45

background image

10 Appendix 2 Parameter Cross Reference

YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide

45

Motor Parameters

Motor Rated Current

E2-01

1.90A*

E2-01

*

* Depends on drive capacity.

Motor Rated Slip

E2-02

2.90 Hz*

E2-02

*

* Depends on drive capacity.

Motor de-coupled load
current

E2-03

1.20A*

E2-03

*

* Depends on drive capacity.

Number of Motor
Poles

E2-04

4-pole

E2-04

4-pole

Motor Line-to-Line
Resistance

E2-05

9.842*

E2-05

*

* Depends on drive capacity.

Motor Leakage
Inductance

E2-06

18.2

E2-06

*

* Depends on drive capacity.

Motor iron core
saturation
Co-efficient 1

E2-07

0.50

E2-07

0.50

Motor iron core
saturation
Co-efficient 2

E2-08

0.75

E2-08

0.75

Motor Mechanical
Loss

E2-09

0.0 %

E2-09

0.0 %

Motor Iron Loss for
Torque Compensation

E2-10

14 W*

E2-10

*

* Depends on drive capacity.

Motor 2 Control Mode

Motor 2 Control
Method Selection

E3-01

2

E3-01

0

E3-01

E3-01

0: V/f

0: V/f

1: V/f w/PG

1: V/f w/PG

2: Open Loop Vector

2: Open Loop Vector

3: Flux Vector Control

3: Closed Loop Vector

Motor 2 V/f
Characteristics

Motor 2 Max
Output Frequency

E4-01

60.0 Hz

E3-04

*

*Determined by control mode selected for motor 2.

Motor 2 Max Voltage

E4-02

230 V*

E3-05

*

*Determined by control mode selected for motor 2.
Double values for 400 V class drives. Multiply by 3 for 600 v
class.

Motor 2 Base
Frequency

E4-03

60.0 Hz

E3-06

*

*Determined by control mode selected for motor 2.

Motor 2 Mid.
Output Frequency

E4-04

3.0 Hz*

E3-07

*

*Determined by control mode selected for motor 2.

Motor 2 Mid. Output
Frequency Voltage

E4-05

12.6 V*

E3-08

*

*Determined by control mode selected for motor 2.
Double values for 400 V class drives. Multiply by 3 for 600 V
class.

Motor 2 Minimum
Output Frequency

E4-06

0.5 Hz*

E3-09

*

*Determined by control mode selected for motor 2.

Motor 2 Minimum
Output Voltage

E4-07

2.3 V*

E3-10

*

*Determined by control mode selected for motor 2.
Double values for 400 V class drives. Multiply by 3 for 600 V
class.

Motor 2 Parameter

Motor 2 Rated Current

E5-01

1.90 A*

E4-01

*

*Depends on drive capacity.

Motor 2 Rated Slip

E5-02

2.90 Hz*

E4-02

*

*Depends on drive capacity.

Motor 2 De-coupled
Load Current

E5-03

1.20 A*

E4-03

*

*Depends on drive capacity.

Motor 2 Poles

E5-04

4-pole

E4-04

4-pole

Motor 2 Line-to-Line
Resistance

E5-05

9.84 Ω*

E4-05

*

*Depends on drive capacity.

Motor 2 Leakage
Inductance

E5-06

18.2 %*

E4-06

*

*Depends on drive capacity

Parameter Name

G5

A1000

Comments (Gray shading indicates default settings)

No.

Default

No.

Default

G5