10 appendix 2 parameter cross reference – Yaskawa GPD515/G5 User Manual
Page 39

10 Appendix 2 Parameter Cross Reference
YASKAWA PL.A1000.01 G5 to A1000 - Product Transition Guide
39
Operation Mode
Selection
Reference Selection
b1-01
1
b1-01
1
b1-01
b1-01
0: Operator
0: Operator
1: Control circuit terminal
(analog input)
1: Control circuit terminal
(analog input)
2: Serial Communication
2: MEMOBUS comm.
3: Option PCB
3: Option PCB
4: EWS
4: Pulse train input
Operation Method
Selection
b1-02
1
b1-02
1
b1-02
b1-02
0: Operator
0: Operator
1: Control circuit terminal
1: Control circuit terminal
2: Serial Communication
2: MEMOBUS comm.
3: Option PCB
3: Option PCB
4: EWS
Not available
Stopping Method
Selection
b1-03
0
b1-03
0
b1-03
b1-03
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: DC Injection Braking
2: DC Injection Braking
3: Coast to stop with timer
3: Coast to stop with timer
Prohibition of Reverse
Operation
b1-04
0
b1-04
0
b1-04
b1-04
0: Reverse possible
0: Reverse possible
1: Reverse prohibited
1: Reverse prohibited
Operation Selection for
setting of E1-09 or
Less
b1-05
0
b1-05
0
b1-05
b1-05
0: Run at frequency reference
0: Run at frequency reference
1: Shut off drive output
1: Shut off drive output
2: Operate by E1-09
2: Operate by E1-09
3: Zero speed
3: Zero speed
Read sequence input
twice
b1-06
1
b1-06
1
b1-06
b1-06
0: 2 ms - 2 scans
0: 1 ms - 1 scan
1: 5 ms - 2 scans
1: 1 ms - 2 scans
Operation Selection
After Switching to
Remote Mode
b1-07
0
b1-07
0
b1-07
b1-07
0: Cycle Run command
0: Cycle Run command
1: Accept external Run cmd
1: Accept external Run cmd
Run Command
Selection in PRG
Mode
b1-08
0
b1-08
0
b1-08
b1-08
0: Disabled.
0: Disabled.
1: Run cmd always accepted
1: Run cmd always accepted
―
2: Cannot enter Program Mode
Run Command at
Power Up
─
─
b1-17
0
0: Prohibited
1: Allowed
Change b1-17 to 1.
DC Injection Braking
Zero speed level (DC
injection braking
starting frequency)
b2-01
0.5 Hz
b2-01
0.5 Hz
―
DC Injection Braking
current
b2-02
50 %
b2-02
50 %
―
DC Injection Braking
Time at Start
b2-03
0.00 s
b2-03
0.00 s
―
DC Injection Braking
Time at Stop
b2-04
0.00 s
b2-04
0.50 s*
*Determined by the control mode selected.
Magnetic Flux
Compensation volume
b2-08
0 %
b2-08
0 %
―
Speed Search
Speed Search Selection
at start
b3-01
0*
b3-01
0*
b3-01
b3-01
0: Disabled
0: Disabled
1: Enabled
1: Enabled
*Default value changes according to the control mode.
Speed Search
Operating Current
b3-02
100 %*
b3-02
120 %*
*Default value changes according to the control mode.
Speed Search
Speed Search
Deceleration Time
b3-03
2.0 s
b3-03
2.0 s
─
Timers
Timer Function On-
Delay Time
b4-01
0.0 s
b4-01
0.0 s
─
Timer Function Off-
Delay Time
b4-02
0.0 s
b4-02
0.0 s
─
Parameter Name
G5
A1000
Comments (Gray shading indicates default settings)
No.
Default
No.
Default
G5
A1000