12 Parameters
Operating Manual
SC500HEUS-eng-BE-BUS120320
85
Ofs_CntFanCab1 * Offset for operating
hours of internal
fan 1
0 h … 2 147 483 h Changing these
parameters may be
necessary if you
replace the
operation control
unit of the Sunny
Central and wish to
transfer the data
from the old device.
You can only view
and change these
parameters using
an installer
password.
‒
Ofs_CntFanCab2* Offset for operating
hours of internal
fan 2
0 h … 2 147 483 h
‒
Ofs_CntFanHs*
Offset for operating
hours of heat sink
fan
0 h … 2 147 483 h
‒
Ofs_CntFanTrf1*
Offset for operating
hours of transformer
fan 1
0 h … 2 147 483 h
‒
Ofs_CntFanTrf2*
Offset for operating
hours of transformer
fan 2
0 h … 2 147 483 h
‒
Ofs_CntHtCab*
Offset for operating
hours of interior
heater
0 h … 2 147 483 h
‒
Offset for total
energy yield of the
Sunny Central
0 kWh …
214 748 364 kWh
‒
Ofs_h-On*
Offset for total
operating hours of
the Sunny Central
0 h … 2 147 483 h
‒
Ofs_h-Total*
Offset for total feed-
in hours of the
Sunny Central
0 h … 2 147 483 h
‒
PvPwrMinTr
Limiting value for
starting the MPP
tracker
0 kW … 1200 kW ‒
20 kW
PvPwrMinTrT
Timeout for starting
the MPP tracker
1 s … 1 800 s
‒
600 s
PVStrT
Timer: target status
switches from
"Wait-PV" to
"Grid-Connect"
when timer expires
1 s … 1 800 s
‒
180 s
Parameters
Description
Value/range
Explanation
Default
value