12 Parameters
SMA America, LLC
80
SC500HEUS-eng-BE-BUS120320
Operating Manual
Qmax*
Limitation of the
reactive power of
the Sunny Central
0 kVAr …
1 000 kVAr
‒
220 kVAr
VArGra*
Gradient of reactive
power change
(VAr/s)
0% … 100%
‒
1%
PF-PF
Displacement
power factor cos φ
0.9 … 1
The lower limit is
defined by the
parameter
"PFAbsMin".
1
PF-PFExt
Excitation of the
displacement
power factor cos φ
OvExt
Overexcited
OvExt
UnExt
Underexcited
PF-PFExtStr*
Excitation of the
displacement
power factor cos φ
at characteristic
curve point 1
OvExt
Overexcited
UnExt
UnExt
Underexcited
PF-PFExtStop*
Excitation of the
displacement
power factor cos φ
at characteristic
curve point 2
OvExt
Overexcited
OvExt
UnExt
Underexcited
Displacement
power factor cos φ
at characteristic
curve point 1
0.5 … 1
The lower limit is
defined by the
parameter
"PFAbsMin".
0.9
PF-PFStop*
Displacement
power factor cos φ
at characteristic
curve point 2
0.5 … 1
The lower limit is
defined by the
parameter
"PFAbsMin".
0.9
PF-WStr*
Sets the feed-in
capacity in % at
characteristic curve
point 1
0% … 90%
‒
0%
PF-WStop*
Sets the feed-in
capacity in % at
characteristic curve
point 2
10% … 100%
‒
100%
Parameters
Description
Value/range
Explanation
Default
value