2 parameters for reactive power regulation, Parameters for reactive power regulation – SMA SC 500HE-US User Manual
Page 77

SMA America, LLC
12 Parameters
Operating Manual
SC500HEUS-eng-BE-BUS120320
77
12.2.2 Parameters for Reactive Power Regulation
Parameters
Description
Value/range
Explanation
Default
value
Q-VAr
Reactive power in
kVAr
− 220 kVAr …
220 kVAr
‒
0 kVAr
Q-VArGra*
Definition of the
change of the
reactive power
target value in the
event of a voltage
step
0% … 100%
The value
corresponds to the
nominal power
"Pmax"
1%
Q-VArGraNom*
Reactive power
gradient
0%/V … 10%/V
‒
1%/V
Specification of the
procedure for
reactive power
regulation
Off
Reactive power
0 kVAr
Displacement
power factor
cos φ=1
Off
VArCtlCom
Limits reactive
power via an
external control
unit, such as the
Power Reducer Box
PFCtlCom
Specifies the
displacement
power factor cos φ
and the excitation
of the displacement
power factor via an
external control
unit, such as the
Power Reducer Box