12  Parameters

Operating Manual

SC500HEUS-eng-BE-BUS120320

77

12.2.2 Parameters for Reactive Power Regulation

Parameters

Description

Value/range

Explanation

Default

value

Q-VAr

Reactive power in
kVAr

− 220 kVAr …

220 kVAr

0 kVAr

Q-VArGra*

Definition of the
change of the
reactive power
target value in the
event of a voltage
step

0% … 100%

The value
corresponds to the
nominal power
"Pmax"

1%

Q-VArGraNom*

Reactive power
gradient

0%/V … 10%/V

1%/V

Q-VArMod*

Specification of the
procedure for
reactive power
regulation

Off

Reactive power
0 kVAr
Displacement
power factor
cos φ=1

Off

VArCtlCom

Limits reactive
power via an
external control
unit, such as the
Power Reducer Box

PFCtlCom

Specifies the
displacement
power factor cos φ
and the excitation
of the displacement
power factor via an
external control
unit, such as the
Power Reducer Box