8 Reactive Power Regulation
SMA America, LLC
46
SC500HEUS-eng-BE-BUS120320
Operating Manual
8.1.11 "VArCtlVol" Procedure
The reactive power is set depending on the line voltage. The reactive power target value is adjusted
in stages.
Figure 14: Characteristic curve for reducing reactive power depending on line voltage
If the line voltage changes by the parameterizable voltage difference "Q-VDif" for the configurable
duration of "Q-VDifTm", the reactive power target value is adapted by the value "Q-VArGr".
The parameterization of this function depends on the medium voltage.
Contact the SMA Service Line before changing any parameters
Contact the SMA Service Line before selecting or configuring the "VArCtlVol" procedure.
Parameters used
"Q-VDif"
"Q-VArGra"
"Q-VDifTm"
"Q-VRtgOfsNom"