10.2.2 Errors 01-13 - Power Distribution Grid Errors

Error number

Cause and corrective measures

01

The line voltage is too high. Error type: Fault (see section 10.2.1 "Error
Types and Waiting Times for Errors", page 56).
Corrective measures:

• Measure the line voltage.

If the line voltage is outside of the permissible range, adjust the line
voltage on the medium-voltage transformer as required.

02

The line voltage is too low. Error type: Fault (see section 10.2.1 "Error
Types and Waiting Times for Errors", page 56).
Corrective measures:

• Measure the line voltage.

If the line voltage is outside of the permissible range, adjust the line
voltage on the medium-voltage transformer as required.

• Ensure that external fuses are functioning.
• Ensure that the AC cables are connected correctly.

05

The power frequency is outside the permitted range. Error type:
Fault (see section 10.2.1 "Error Types and Waiting Times for
Errors", page 56).
Corrective measures:

• Measure the line voltage.

If the line voltage is outside of the permissible range, adjust the line
voltage on the medium-voltage transformer as required.

• Ensure that external fuses are functioning.
• Ensure that the AC cables are connected correctly.

08

A line conductor has failed. Error type: Fault (see section 10.2.1 "Error
Types and Waiting Times for Errors", page 56).
Corrective measures:

• Measure the line voltage.

If the line voltage is outside of the permissible range, adjust the line
voltage on the medium-voltage transformer as required.

• Ensure that external fuses are functioning.
• Ensure that the AC cables are connected correctly.