12  Parameters

SMA America, LLC

82

SC500HEUS-eng-BE-BUS120320

Operating Manual

HzCtlllLim***

Underfrequency
limiting value
level 2

57 Hz … 59.8 Hz Changing this

parameter results in
the loss of UL
certification.

57 Hz

HzCtllLimTm*

Tripping time for
underfrequency
level 1

160 ms …

300 000 ms

160 ms

HzCtlllLimTm***

Tripping time for
underfrequency
level 2

0 ms …

1 000 000 ms

Changing this
parameter results in
the loss of UL
certification.

160 ms

HzCtlOpMax*

Maximum
connection
frequency

60 Hz … 66 Hz

60.5 Hz

HzCtlOpMin*

Minimum
connection
frequency

54 Hz … 60 Hz

59.3 Hz

VRtg**

Nominal line
voltage of the
power distribution
grid

1 V … 70 000 V

200 V

VCtlhLim***

Limiting value for
overvoltage
tripping level 1

100% … 150%

The value is based
on the nominal
voltage of the
inverter. Changing
this parameter
results in the loss of
UL certification.

110%

VCtlhhLim***

Limiting value for
overvoltage
tripping level 2

100% … 150%

120%

VCtlhLimTm***

Tripping time for
overvoltage level 1

0 ms …

1 000 000 ms

Changing this
parameter results in
the loss of UL
certification.

1 000 ms

VCtlhhLimTm***

Tripping time for
overvoltage level 2

0 ms …

1 000 000 ms

160 ms

VCtllLim***

Limiting value for
undervoltage
tripping level 1

0% … 100%

The value is based
on the nominal
voltage of the
inverter. Changing
this parameter
results in the loss of
UL certification.

88%

VCtlllLim***

Limiting value for
undervoltage
tripping level 2

0% … 100%

50%