SMA SC 500HE-US User Manual
Page 68

12 Parameters
SMA America, LLC
68
SC500HEUS-eng-BE-BUS120320
Operating Manual
P-W
Limits the active
power in kW
0 kW … 500 kW
The active power
cannot exceed
"Pmax".
500 kW
P-WNom
Limits the active
power in %
0% … 100%
‒
100%
P-WMod*
Procedure selection
for active power
limitation
Off
Limits active power
to "Pmax"
WCnst
WCtlCom
Limits active power
via an external
control unit, such as
the Power Reducer
Box
WCnst
Manually limits the
active power in kW
(P-W) via
communication
devices such as the
Sunny WebBox
WCnstNom
Manually limits the
active power in %
(P-WNom) via
communication
devices such as the
Sunny WebBox
WCnstNomAnIn
Limits active power
in % on the analog
input
PF-PF
Displacement
power factor cos φ
0.9 … 1
The lower limit is
defined by the
parameter
"PFAbsMin".
1
PF-PFExt
Excitation of the
displacement
power factor cos φ
OvExt
Overexcited
OvExt
UnExt
Underexcited
PF-PFExtStr*
Excitation of the
displacement
power factor cos φ
at characteristic
curve point 1
OvExt
Overexcited
UnExt
UnExt
Underexcited
Parameters
Description
Value/range
Explanation
Default
value