8 Reactive Power Regulation
SMA America, LLC
44
SC500HEUS-eng-BE-BUS120320
Operating Manual
8.1.9 "PFCnstAnIn" Procedure
The reactive power target value is set at the input terminals using an analog signal for specifying the
target value (see the inverter installation manual). This is usually implemented by a ripple control
receiver.
The analog value is converted into a displacement power factor cos φ. The electrical current strength
of the connected signal determines the target value.
The analog measured values must be between 4 mA and 19 mA. If the analog signal is less than
2 mA, the error message will be displayed in the instantaneous value "Q-VArModFailStt".
The analog value is converted into a target value for the displacement power factor cos φ. Here, the
parameter "PFAbsMin" is the start and end point of the linear characteristic curve.
Signal
Power limit
Description
< 2 mA
Last valid value,
or 1 after restart
Signal is in the invalid range.
2 mA … 4 mA
"PFAbsMin"/underexcited
The maximum amount of negatively
excited reactive power is fed in.
4 mA
"PFAbsMin"/underexcited
Starting point of the curve
Maximum amount of negatively excited
reactive power is fed in.
11.5 mA
1
Zero-crossing of the curve
No reactive power is fed in.
> 19 mA
"PFAbsMin"/overexcited
End point of the curve
Maximum amount of positively excited
reactive power is fed in.
Parameter used
"PFAbsMin"