SMA SC 500HE-US User Manual
Page 66

12 Parameters
SMA America, LLC
66
SC500HEUS-eng-BE-BUS120320
Operating Manual
CntHtCab
Operating hour
meter of interior
heater
CntAcSw
Meter for the
switching operations
of the AC contactor
CntDcSw
Meter for the
switching operations
of the DC contactor
Dt
Date
‒
Format yyyymmdd
‒
EnaAid*
Enables islanding
detection
Off
Deactivated
On
On
Activated
HzCtlhLim***
Overfrequency
limiting value
level 1
60.5 Hz … 64.5 Hz Changing this
parameter results in
the loss of UL
certification.
60.5 Hz
Overfrequency
limiting value level 2
60 Hz … 66 Hz
‒
65 Hz
HzCtlhLimTm*** Tripping time for
overfrequency
level 1
0 ms …
1 000 000 ms
Changing this
parameter results in
the loss of UL
certification.
160 ms
Tripping time for
overfrequency
level 2
0 ms …
1 000 000 ms
‒
100 ms
HzCtllLim*
Underfrequency
limiting value level 1
57.0 Hz … 59.8 Hz ‒
59.3 Hz
HzCtlllLim***
Underfrequency
limiting value level 2
57 Hz … 59.8 Hz Changing this
parameter results in
the loss of UL
certification.
57 Hz
HzCtllLimTm*
Tripping time for
underfrequency
level 1
160 ms …
300 000 ms
‒
160 ms
Parameters
Description
Value/range
Explanation
Default
value