SMA SC 500HE-US User Manual
Page 73

SMA America, LLC
12 Parameters
Operating Manual
SC500HEUS-eng-BE-BUS120320
73
Qmax*
Limitation of the
reactive power of
the Sunny Central
0 kVAr …
1 000 kVAr
‒
220 kVAr
Serial Number** Inverter serial
number
0 … 2147483647 ‒
‒
SpntRemEna
Enables the plant
remotely
Off
Deactivated
On
On
Activated
VArGra*
Gradient of reactive
power change
(VAr/s)
0% … 100%
‒
1%
VCtlhLim***
Limiting value for
overvoltage
tripping level 1
100% … 150%
Changing this
parameter results in
the loss of UL
certification.
110%
VCtlhhLim***
Limiting value for
overvoltage
tripping level 2
100% … 150%
120%
VCtlhLimTm***
Tripping time for
overvoltage level 1
0 ms …
1 000 000 ms
1 000 ms
VCtlhhLimTm***
Tripping time for
overvoltage level 2
0 ms …
1 000 000 ms
160 ms
Limiting value for
undervoltage
tripping level 1
0% … 100%
88%
VCtlllLim***
Limiting value for
undervoltage
tripping level 2
0% … 100%
50%
Tripping time for
undervoltage
level 1
0 ms …
1 000 000 ms
2 000 ms
VCtlllLimTm***
Tripping time for
undervoltage
level 2
0 ms …
1 000 000 ms
160 ms
VCtlOpMinNom* Minimum
connection voltage
0% … 100%
‒
95%
VCtlOpMaxNom* Maximum
connection voltage
100% … 200%
‒
106%
Parameters
Description
Value/range
Explanation
Default
value