beautypg.com

SMA SC 500HE-US User Manual

Page 73

background image

SMA America, LLC

12  Parameters

Operating Manual

SC500HEUS-eng-BE-BUS120320

73

Qmax*

Limitation of the
reactive power of
the Sunny Central

0 kVAr …

1 000 kVAr

220 kVAr

Serial Number** Inverter serial

number

0 … 2147483647 ‒

SpntRemEna

Enables the plant
remotely

Off

Deactivated

On

On

Activated

VArGra*

Gradient of reactive
power change
(VAr/s)

0% … 100%

1%

VCtlhLim***

Limiting value for
overvoltage
tripping level 1

100% … 150%

Changing this
parameter results in
the loss of UL
certification.

110%

VCtlhhLim***

Limiting value for
overvoltage
tripping level 2

100% … 150%

120%

VCtlhLimTm***

Tripping time for
overvoltage level 1

0 ms …

1 000 000 ms

1 000 ms

VCtlhhLimTm***

Tripping time for
overvoltage level 2

0 ms …

1 000 000 ms

160 ms

VCtllLim***

Limiting value for
undervoltage
tripping level 1

0% … 100%

88%

VCtlllLim***

Limiting value for
undervoltage
tripping level 2

0% … 100%

50%

VCtllLimTm***

Tripping time for
undervoltage
level 1

0 ms …

1 000 000 ms

2 000 ms

VCtlllLimTm***

Tripping time for
undervoltage
level 2

0 ms …

1 000 000 ms

160 ms

VCtlOpMinNom* Minimum

connection voltage

0% … 100%

95%

VCtlOpMaxNom* Maximum

connection voltage

100% … 200%

106%

Parameters

Description

Value/range

Explanation

Default

value