beautypg.com

Error messages and warnings for the reactive power, Setpoint – SMA SC 500HE-US User Manual

Page 50

background image

8  Reactive Power Regulation

SMA America, LLC

50

SC500HEUS-eng-BE-BUS120320

Operating Manual

8.2 Error Messages and Warnings for the Reactive Power Setpoint

The instantaneous value "Q-VArModFailStt" displays errors or warnings relating to the reactive power
setpoint.

• Display the instantaneous value

"

Q-VArModFailStt" on the Sunny WebBox user interface (see

section 6.1 "Displaying the Instantaneous Values", page 34).

Display

Cause and corrective measures

"Off"

No procedure for specifying the reactive power setpoint has been selected.

"Ok"

A procedure for specifying the reactive power setpoint has been selected and there
are no errors.

"ComFail"

The procedure "VArCtlCom" or "PFCtlCom" has been selected and the expected
signal with a valid reactive power setpoint has been absent for at least 5 minutes.
Corrective measures:

• Ensure that the Sunny WebBox and the Power Reducer Box can be accessed

via the Internet.

• Ensure that the Sunny WebBox is connected correctly.
• Ensure that the cabling between the Sunny WebBox and the inverter is OK.

"AnInFail"

The procedure "VArCnstNomAnIn" or "PFCnstNomAnIn" has been selected and the
value measured at the analog input is less than 2mA.
Corrective measures:

• Ensure that the signal cable is correctly connected to the analog input.

This manual is related to the following products: