12.2.3 Parameters for Grid Monitoring
PFAbsMin**
Limitation of the
displacement
power factor cos φ
0.5 … 1
‒
0.9
Q-EnaTmsVtg*
Connection delay
of line voltage
Off
‒
Off
On
‒
* This parameter can only be changed after the installer password has been entered.
** This is a read‑only parameter.
Loss of UL certification
The limiting values for the line voltage and the power frequency are configured in accordance
with IEEE 1547. Changes to the factory-configured limiting values result in the loss of UL
certification. The parameters for these limiting values are marked with ***.
• If the UL certification is the deciding factor for the operation permission of the inverter, do
not make any changes to the factory-configured limiting values for the grid monitoring
parameters.
Parameters
Description
Value/range
Explanation
Default
value
HzCtlhLim***
Overfrequency
limiting value
level 1
60.5 Hz … 64.5 Hz Changing this
parameter results in
the loss of UL
certification.
60.5 Hz
HzCtlhhLim*
Overfrequency
limiting value
level 2
60 Hz … 66 Hz
‒
65 Hz
HzCtlhLimTm***
Tripping time for
overfrequency
level 1
0 ms …
1 000 000 ms
Changing this
parameter results in
the loss of UL
certification.
160 ms
Tripping time for
overfrequency
level 2
0 ms …
1 000 000 ms
‒
100 ms
HzCtllLim*
Underfrequency
limiting value
level 1
57 Hz … 59.8 Hz ‒
59.3 Hz
Parameters
Description
Value/range
Explanation
Default
value