SMA SC 500HE-US User Manual
Page 79

SMA America, LLC
12 Parameters
Operating Manual
SC500HEUS-eng-BE-BUS120320
79
VArCtlVolHystDb
Specifies the
reactive power
depending on the
line voltage
(Q = f(U)
characteristic curve)
Q-VArNom
Reactive power in
%
− 100% … 100% ‒
0%
Q-VArTmsSpnt*
Time setting of the
characteristic curve
point
1 s … 60 s
‒
10 s
Q-VArTmsVtg*
Delay of line
voltage
1 s … 60 s
‒
10 s
Q-VDif*
Definition of the
voltage change that
leads to a reactive
power change.
0.1% … 10%
The value
corresponds to the
nominal voltage
"VRtg".
1%
Q-VDifTm*
Time span in which
a voltage change
must be present
before the reactive
power target value
"Q-VArGra"
changes.
0 s … 120 s
‒
1 s
Q-VolNomP1*
Voltage at point 1
80% … 120%
‒
100%
Q-VolNomP2*
Voltage at point 1
80% … 120%
‒
100%
Q-VolWidNom*
Voltage width
0% … 20%
‒
0%
Changes the
nominal voltage
"VRtg" of the
voltage-dependent
reactive power
regulation
− 10% … 10%
The parameter is
active only if the
parameter
"Q-VArMod" is set
to "VArCtlVol".
0%
Qlimit**
Definition of the
reactive power of
the Sunny Central
0 kVAr …
1 000 kVAr
‒
220 kVAr
Parameters
Description
Value/range
Explanation
Default