12  Parameters

Operating Manual

SC500HEUS-eng-BE-BUS120320

83

12.2.4 Parameters for Grid Support

VCtllLimTm***

Tripping time for
undervoltage
level 1

0 ms …

1 000 000 ms

Changing this
parameter results in
the loss of UL
certification.

2 000 ms

VCtlllLimTm***

Tripping time for
undervoltage
level 2

0 ms …

1 000 000 ms

160 ms

VCtlOpMinNom*

Minimum
connection voltage

0% … 100%

95%

VCtlOpMaxNom* Maximum

connection voltage

100% … 200%

106%

* This parameter can only be changed after the installer password has been entered.

** This is a read‑only parameter.

*** Changing this parameter results in the loss of UL certification.

Loss of UL certification

Deactivation of the islanding detection results in the loss of UL certification and SMA is not
liable for any resulting damage.

Parameters

Description

Value/range

Explanation

Default

value

EnaAid*

* This parameter can only be changed after the installer password has been entered.

Enables islanding
detection

Off

Deactivated

On

On

Activated

Parameters

Description

Value/range

Explanation

Default

value