12  Parameters

Operating Manual

SC500HEUS-eng-BE-BUS120320

67

HzCtlllLimTm***

Tripping time for
underfrequency
level 2

0 ms …

1 000 000 ms

Changing this
parameter results in
the loss of UL
certification.

160 ms

HzCtlOpMax*

Maximum
connection
frequency

60 Hz … 66 Hz

60.5 Hz

HzCtlOpMin*

Minimum
connection
frequency

54 Hz … 60 Hz

59.3 Hz

Ofs_CntFanCab1* Offset for operating

hours of internal
fan 1

0 h … 2 147 483 h Changing this

parameter may be
necessary if you
replace the
operation control
unit of the Sunny
Central and wish to
transfer the data
from the old device.
You can only view
and change this
parameter using an
installer password.

Ofs_CntFanCab2* Offset for operating

hours of internal
fan 2

0 h … 2 147 483 h

Ofs_CntFanHs*

Offset for operating
hours of heat sink
fan

0 h … 2 147 483 h

Ofs_CntFanTrf1* Offset for operating

hours of transformer
fan 1

0 h … 2 147 483 h

Ofs_CntFanTrf2* Offset for operating

hours of transformer
fan 2

0 h … 2 147 483 h

Ofs_CntHtCab*

Offset for operating
hours of interior
heater

0 h … 2 147 483 h

Ofs_E-Total*

Offset for total
energy yield of the
Sunny Central

0 kWh …

214 748 364 kWh

Ofs_h-On*

Offset for total
operating hours of
the Sunny Central

0 h … 2 147 483 h

Ofs_h-Total*

Offset for total feed-
in hours of the
Sunny Central

0 h … 2 147 483 h

Parameters

Description

Value/range

Explanation

Default

value