10  Troubleshooting

SMA America, LLC

60

SC500HEUS-eng-BE-BUS120320

Operating Manual

10.2.5 Communication Errors

If the text line displays "No Communication", a communication error has occurred. The communication
error is displayed without the two-digit error number.

76

An internal communication error has occurred. Error type: Error 1 (see section

10.2.1 "Error Types and Waiting Times for Errors", page 56).
Corrective measures:

• Contact the SMA Service Line.

77

A contactor error has occurred. Error type: Defect (see section 10.2.1 "Error

Types and Waiting Times for Errors", page 56).
Corrective measures:

• Contact the SMA Service Line.

78

The surge arrester has tripped. Error type: Warning (see section 10.2.1 "Error

Types and Waiting Times for Errors", page 56).
Corrective measures:

• Replace the defective module of the surge arrester.

79

A reverse current has occurred in the PV array. Error type: Error 2 (see section

10.2.1 "Error Types and Waiting Times for Errors", page 56).
Corrective measures:

• Contact the SMA Service Line.

87

The power setpoint outside of the valid range. Error type: Warning (see section

10.2.1 "Error Types and Waiting Times for Errors", page 56).
Corrective measures:

• Ensure that the power setpoint is correct.

Error number

Cause and corrective measures

None

The display has received no data for 5 minutes.
Corrective measures:

• Ensure that the data cable is connected correctly.
• Ensure that there is supply voltage to the operation control unit.
• Contact the SMA Service Line.

Error number

Cause and corrective measures