13 Technical Data
In this section you will find the technical data for the Sunny Central's operation, the norms to which it
conforms and the required cables and torques.
PV Generator Connection Data
Grid Connection Data
General Data
DC input voltage
300 ... 600 V DC
Input voltage, MPP range
330 ... 600 V DC
DC starting voltage
400 V DC (adjustable)
Max. input current
1,600 A
DC voltage ripple (peak to peak)
< 3 %
Nominal output power (at 77 °F (25 °C))
500 kW
Nominal output power (at 113 °F (45 °C))
500 kW
Output power at 300 V DC
460 kW
Nominal AC voltage
Operating range
480 V AC
422 ... 528 V AC
AC nominal frequency
Operating range
60 Hz
59.3 ... 60.5 Hz
Max. AC current
601.4 A AC (at 480 V AC)
Inverter technology
True sine wave, current source, high frequency
PWM with galvanic insulation
Max. operating altitude
13,000 ft. (4,000 m) above sea level
Power Reduction:
The Sunny Central can function without power
reduction up to 3,300 feet (1,000 m) above sea
level. At higher altitudes the power is reduced by
5 % per 3,300 ft (1,000 m).
Ambient temperatures
-13 °F ...113 °F (-25 °C ... 45 °C) (without
power reduction)
-13 °F ... 122 °F (-25 °C ... 50 °C) (with power
reduction)
Output power at 122 °F (50 °C) = approx.
347 kW
Cooling
Temperature-controlled fans for cooling. Easily
removable filters, easily accessible.