13 Technical Data

In this section you will find the technical data for the Sunny Central's operation, the norms to which it
conforms and the required cables and torques.

PV Generator Connection Data

Grid Connection Data

General Data

DC input voltage

300 ... 600 V DC

Input voltage, MPP range

330 ... 600 V DC

DC starting voltage

400 V DC (adjustable)

Max. input current

1,600 A

DC voltage ripple (peak to peak)

< 3 %

Nominal output power (at 77 °F (25 °C))

500 kW

Nominal output power (at 113 °F (45 °C))

500 kW

Output power at 300 V DC

460 kW

Nominal AC voltage
Operating range

480 V AC
422 ... 528 V AC

AC nominal frequency
Operating range

60 Hz
59.3 ... 60.5 Hz

Max. AC current

601.4 A AC (at 480 V AC)

Inverter technology

True sine wave, current source, high frequency
PWM with galvanic insulation

Max. operating altitude

13,000 ft. (4,000 m) above sea level
Power Reduction:
The Sunny Central can function without power
reduction up to 3,300 feet (1,000 m) above sea
level. At higher altitudes the power is reduced by
5 % per 3,300 ft (1,000 m).

Ambient temperatures

-13 °F ...113 °F (-25 °C ... 45 °C) (without
power reduction)
-13 °F ... 122 °F (-25 °C ... 50 °C) (with power
reduction)
Output power at 122 °F (50 °C) = approx.
347 kW

Cooling

Temperature-controlled fans for cooling. Easily
removable filters, easily accessible.