• For installing the Sunny Central in closed rooms an air supply of 2090 CFM (3,550 m³ /h) is

needed.

• For more information see section 13 "Technical Data" (page 69).

5.1.4 Minimum Clearance

Observe the specified minimum clearances for the cables, ventilation and for opening the doors. For
installing the Sunny Central in closed rooms an air supply of 2090 CFM (3,550 m³ /h) is needed.

5.1.5 Characteristics of the Base

• The foundation must be made of concrete.
• The mounting surface must be level and strong

enough to support the weight of the inverter. The
evenness of the foundation must be less than
0.25 %.

• The width and depth of the base must be at least the

same size as the Sunny Central.

• To insert the cables from below, the cable conduits

must be laid in the foundation (see section
6.2 "Insert cables from below into the Sunny
Central" (page 36)).

Position

Cables inserted from ...

Minimum clearance

A

below

6 in. (15 cm)

B

the side

47 in. (120 cm)

6 in.

6 in.

47 in.

47 in.

6 in.

16 in.

Stop S

tart

A

B

min. 145

in.

min. 40

in.

Stop S

tart