SMA Solar Technology AG

46

SC500U-IUS093411

Installation Guide

8.3 Connection Options

There are various options for connecting the Sunny Central to the public grid and the PV modules.
When placing your order these options will enable you to adapt the Sunny Central connection area
to the characteristics of the PV modules and the grid. This section demonstrates the various connection
options.

8.3.1 Grid Types

The Sunny Central can be connected to the following grids:

• 480 Delta:277 WYE (preset)
• 480 Delta

The figure below illustrates the grid types.

8.3.2 DC Fuses

The Sunny Central can be delivered with 6, 7, 8 or 9 DC fuses. Every fuse has a separate rail to which
1 or 2 DC strings can be connected.

8.3.3 Grounding the PV modules

Depending on the configuration option, you can connect positive or negative grounded PV modules
to the Sunny Central.

DANGER

During operation, high voltages are present in the Sunny Central.
Death resulting from burning and electric shock.

• The cofiguration of the Sunny Central for another grid may only be maintained by

SMA service personnel. Contact the SMA Serviceline for support (see section
14 "Contact" (page 72)).

480 V

480 V

480 V

480 V

480 V

480 V

277 V

277 V

277 V

N

A

A

C

B

C

B