8.6.2 Connecting AC

1. Pay close attention to all safety precaution measures regarding the low voltage grid.
2. Switch off the AC disconnect and secure it against accidental switching on.
3. Ensure that no voltage is present.
4. Open the Sunny Central as described in Section 10 "Opening the Sunny Central" (page 60).
5. Lead the cables into the Sunny Central as described in Section 6 "Attaching the Conduits"

(page 35).

6. Connect ground cables to the terminal blocks at the

bottom right of the Sunny Central.

7. Open the screw terminal completely.
8. Plug the copper inner conductor of the cable into the

screw terminal.

9. Tighten the screw terminal using an Allen key. The

required torque is 42 ft-lbs (57 Nm).

10. Connect all grounding cables of the modules as

described above.

DANGER

High voltages are present in the live components of the low voltage grid.
Death resulting from burning and electric shock.

11. Open the AC terminals completely.
12. Connect phase A to the terminal marked "A". Tighten

the screw terminal using an Allen key. The required
torque is 42 ft-lbs (57 Nm).

A

Stop S

tart

4

3