SMA Solar Technology AG

Installation Guide

SC500U-IUS093411

65

ChkGdVtgLo

149.6 ... 265.9
Vrms

243.8 Vrms

Minimum voltage for Sunny Central
operation.
The Sunny Central shuts down within 2
seconds in case the voltage exceeds the
value defined in ChkGdVtgLo.

ChkGdVtgMax

288 ... 332,4 Vrms 332,4 Vrms

Maximum voltage for Sunny Central
operation.
If the voltage exceeds the value defined
in ChkGdVtgMax, the Sunny Central
shuts down immediately.

ChkGdVtgMin

138,5 ... 265,9 Hz 138,5 Hz

Minimum voltage for Sunny Central
operation.
If the voltage drops below the value
defined at ChkGdVtgMin, the Sunny
Central shuts down immediately.

ChkGnFrqLo

Sunny Central operation with a
generator.
More information on parameter settings
and operating the Sunny Central with a
generator can be obtained from SMA
America.

ChkGnFrqLoT
ChkGnFrqMax
ChkGnFrqMin
ChkGnVtgHi
ChkGnVtgLo
ChkGnVtgMax
ChkGnVtgMin
CtlExtPwrKi

Parameter name Range

Default

Parameter Description