Installation Guide
8.6 AC Connection
8.6.1 Requirements
The AC input and AC output circuits are isolated from the enclosure and the system grounding, if
required by Section 250 of the National Electrical Code, ANSI/NFPA 70, is the responsibility of the
installer.
Technical Data for the AC Connection
Connection to the AC Grid
CAUTION
Improper connection to the public grid may cause a fire.
Burns from fire.
To reduce the risk of fire,
• connect only to a circuit provided with 900 amperes maximum branch-circuit
overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA
70.
• do not connect to an AC load center (circuit breaker panel) having multiwire branch
circuits connected.
Nominal AC voltage
480 V AC
Max. AC current
601.4 A
Number of AC
Cables
Cable Size
Torque
A, B, C
6
400 kcmil
All 194 °F (90 °C) copper wire,
42 ft-lbs (57 Nm) tightening torque
N
(only for 480
Delta:277
WYE)
1 or 2
4 AWG – 600 kcmil All 194 °F (90 °C) copper wire,
42 ft-lbs (57 Nm) tightening torque
PE
1
3/0 AWG –
600 kcmil
42 ft-lbs (57 Nm)