SMA Solar Technology AG

52

SC500U-IUS093411

Installation Guide

8.6 AC Connection

8.6.1 Requirements

The AC input and AC output circuits are isolated from the enclosure and the system grounding, if
required by Section 250 of the National Electrical Code, ANSI/NFPA 70, is the responsibility of the
installer.

Technical Data for the AC Connection

Connection to the AC Grid

CAUTION

Improper connection to the public grid may cause a fire.
Burns from fire.
To reduce the risk of fire,

• connect only to a circuit provided with 900 amperes maximum branch-circuit

overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA
70.

• do not connect to an AC load center (circuit breaker panel) having multiwire branch

circuits connected.

Nominal AC voltage

480 V AC

Max. AC current

601.4 A

Number of AC

Cables

Cable Size

Torque

A, B, C

6

400 kcmil

All 194 °F (90 °C) copper wire,

42 ft-lbs (57 Nm) tightening torque

N

(only for 480

Delta:277

WYE)

1 or 2

4 AWG – 600 kcmil All 194 °F (90 °C) copper wire,

42 ft-lbs (57 Nm) tightening torque

PE

1

3/0 AWG –

600 kcmil

42 ft-lbs (57 Nm)