Cleanness, Cooling – H3C Technologies H3C SecPath F1000-E User Manual

Page 16

background image

8

Item Temperature

Storage temperature

–40°C to +70°C (–40°F to +158°F)

Table 2 Humidity requirements

Item Relative

humidity

Operating humidity

10% to 95%, noncondensing

Storage humidity

5% to 95%, noncondensing

Cleanness

Dust buildup on the chassis may result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,

electrostatic adsorption can cause communication failure.

Table 3 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 4

.

Table 4 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Cooling

The firewalls adopt left to right airflow for heat dissipation. Plan the installation site for adequate
ventilation.

Leave at least 10 cm (3.94 in) of clearance at the inlet and outlet air vents.

The installation site has a good cooling system.