Grounding the switch by using the ac power cord, Grounding the switch – H3C Technologies H3C S5560 Series Switches User Manual
Page 29
20
Figure 25 Grounding the switch by burying the grounding conductor into the earth ground
(1) Grounding screw
(2) Chassis rear panel
(3) Grounding cable
(4) Earth
(5) Joint
(6) Grounding conductor
Grounding the switch by using the AC power cord
If the installation site has no grounding strips or earth ground, you ground an AC-powered switch through
the PE wire of the power cord. Make sure:
•
The power cord has a PE terminal.
•
The ground contact in the power outlet is securely connected to the ground in the power distribution
room or on the AC transformer side.
•
The power cord is securely connected to the power outlet.
NOTE:
If the ground contact in the power outlet is not connected to the ground, report the problem and reconstruct
the grounding system.
1
2
3
4
5
6