N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
Air, Water or Remote Service Manual

December 2014

Page 43

Symptom

Probable Cause

Possible Correction

Low ice making capacity

Scale build up

Remove scale from evaporator and

water system

Restricted water to evaporator

Check for air bubble in hose to

evaporator. If there is an air bubble

AND the reservoir has a water

sensor IN the bowl, replace the

reservoir.

High discharge pressure

Check remote condenser
Check headmaster

Expansion valve superheat

incorrect

Check superheat

Compressor cycles on and off

frequently

Check liquid line valve for leak

through
May be normal, pump down switch

will operate compressor as pump

down switch closes and opens

Service Diagnosis - Remote Air Cooled