N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
Air, Water or Remote Service Manual
December 2014
Page 13
Remote condenser models have additional installation
needs.
The correct remote condenser fan and coil must
be connected to the ice making head. Liquid and
discharge tubing connections are on the back of the
ice machine cabinet. Pre-charged tubing kits are
available in several lengths to accommodate most
installations. Order the one that just exceeds the
length needed for the installation.
The kit numbers are:
• RTE10
• RTE25
• RTE40
• RTE75
There are limits as to how far away from the ice
machine and where the remote condenser can be
located. See the next page for those limits.
The correct condenser must be used.
Ice Machine Model
Condenser Model
F0822R-1
ERC111-1
F1222R-32, F1222R-3
ERC311-32
N0622R-1, N0822R-1
ERC111-1
N0922R-32, N1222R-3
ERC311-32
N1322R-32
ERC311-32
Note: A headmaster is required for all remote
condenser systems. Prior condensers did not have
a headmaster. New head / old condenser retrofits
can use headmaster kit KPFHM. See chart below for
applications.
Refrigeration - Remote Condenser Models
Prior Head
Prior Condenser New Head
NME654R
ERC101
N0622R
FME804R
ERC101
F0822R
NME954R
ERC151
N0922R
FME1204R
ERC151
F1222R
NME1254R
ERC201
N1322R
FME1504R
ERC201
F1522R
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will
cause compressor failure and will void the warranty.