Scotsman Prodigy Plus D Series Service Manual User Manual

Page 13

background image

N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
Air, Water or Remote Service Manual

December 2014

Page 13

Remote condenser models have additional installation

needs.

The correct remote condenser fan and coil must

be connected to the ice making head. Liquid and

discharge tubing connections are on the back of the

ice machine cabinet. Pre-charged tubing kits are

available in several lengths to accommodate most

installations. Order the one that just exceeds the

length needed for the installation.

The kit numbers are:

• RTE10

• RTE25

• RTE40

• RTE75

There are limits as to how far away from the ice

machine and where the remote condenser can be

located. See the next page for those limits.

The correct condenser must be used.

Ice Machine Model

Condenser Model

F0822R-1

ERC111-1

F1222R-32, F1222R-3

ERC311-32

N0622R-1, N0822R-1

ERC111-1

N0922R-32, N1222R-3

ERC311-32

N1322R-32

ERC311-32

Note: A headmaster is required for all remote

condenser systems. Prior condensers did not have

a headmaster. New head / old condenser retrofits

can use headmaster kit KPFHM. See chart below for

applications.

Refrigeration - Remote Condenser Models

Prior Head

Prior Condenser New Head

NME654R

ERC101

N0622R

FME804R

ERC101

F0822R

NME954R

ERC151

N0922R

FME1204R

ERC151

F1222R

NME1254R

ERC201

N1322R

FME1504R

ERC201

F1522R

Do not reuse condenser coils contaminated with

mineral oil (used with R-502 for example). They will

cause compressor failure and will void the warranty.