Troubleshooting | 82

SEP Faults

The self-diagnostic system built into the SEP can display some fault conditions by flashing the
yellow “Service” LED in sequence. The SEP does not display any warnings.

Faults

If the humidifier is not able to self correct a problem symptom it will if necessary respond by

shutting itself down.

When this occurs the humidifier illuminates the red “Fault” LED, Flashes the yellow LED in a

numerical sequence, shuts off the signal to the CV valve actuator, and activates the “Error”
relay of the remote relay board.

Clearing a Fault

Count the number of flashes of the yellow LED and take any necessary actions to correct the

cause(s) as outlined in Table 14: Troubleshooting SEP Faults.

Power cycle the humidifier with the On/Off switch waiting 3 seconds between turning it off

and on.

Table 14: Troubleshooting SEP Faults

Number of

Flashes / Fault

System Detected

Cause

Corrective Action(s)

One Flash
Humidifier Drain
Fault

Water level is not
dropping when
pump is activated.

1 Internal drain

blocked

Check if water drains from unit when drain
manually activated. If not then;
1a Check restrictor in drain line immediately after

pump for blockage.

1b Check pump rotor to see if it is blocked.
1c Check if scale has built up in sump at bottom of

tank and caused a blockage.

2 External drain

blocked

2 Check that water can flow freely through drain

lines.

Two Flashes
Humidifier Fill
Fault

Water level not
rising or not
detected.

1 Water shut off

valve closed

1 Open shut off valve

2 Auxiliary drain

leaking

2a Close auxiliary drain valve if unit does not have

freeze protection.

2b Check freeze protection valve is closed if freeze

protection installed.

3 Fill valve

strainer blocked

3 Clean out strainer on fill valve inlet.

Four Flashes
Inconsistent
Float Level

Floats have
indicated water
level not changing
in sequence.

1 High cooling

flow into float
chamber

1a Check that orifice in fill valve is in place. Flow

should be very low.

1b Check if tank fill and float cooling lines are

reversed. Flow to float chamber should be very
low. Tank hoses to centre of float chamber.

2 Defective float

board.

2 Observe LED’s on float chamber as tank fills. If

LED’s do not light in sequence replace float
chamber and float board.