19 | Installation





















Figure 14: Distributor Location in Duct





























Figure 15: SAM-e/Steam Distributor Above Humidifier (Copper Steam Line Shown)

12 in.

(30 cm)

min.

Calculated absorption

distance to any obstruction

or 8-10 ft (2.4 - 3 m)

if unknown

Mount distributor

to side of duct

2 x duct

height min.

2/3 Duct
height

Note:
Refer to distributor or SAM-e installation manuals for detailed installation instructions.

Hose cuff

with clamps

2 in. (5 cm)

min.

1 ft (30 cm)

‘P’ Trap

1 ft (30 cm)

min. before

anybend

Condensate line

Use steam hose between
steam outlet and steam line.

Insulated copper

steam line. Support

so weight is not on

steam outlet.

To drain