81 | Troubleshooting

Code

Display

Message

LED

System Detected

Cause

Corrective Action(s)

5 Humidifier control

configuration incorrect

5 Check that the

humidifier control
configuration matches
the installed sensor
output.

TCF

Tank Cold Fault

Red

The tank has not
become hot with
the steam valve
activated.

1 Tank temperature

sensor not detecting
warm tank.

1b Check tank to see if hot

(caution).

1a Check wiring to tank

temperature sensor.

1c Check if sensor closed

when tank is hot.

TCW

2 No steam supply to

humidifier.

2a Check that isolation

valve is not closed.

2b Check if boiler steam is

available.

2c Check if CV valve opens

using diagnostic output
test.

3 Condensate not

draining from heat
exchanger.

3a Check that F&T trap is

allowing condensate to
drain.