15 | Installation

Boiler Steam and Boiler Condensate Return

Figure 10: SE Boiler Steam and Condensate Connection

Note:.

Pressurized steam line installation to be performed by a qualified installer.

Damage to SE heat exchanger will occur if it is exposed to pressure above 20 psi..

A safety relief valve must be installed to prevent the SE from being exposed to

pressure in excess of 15 psi when the SE is connected to a medium or high

pressure boiler via a pressure reducing valve.

The steam supply line must be designed to provide design pressure at the CV valve

when there is 100 % demand (CV valve completely open). Pressure losses in the

steam supply line will reduce SE output.

Condensate must be drained to a non-pressurized boiler condensate return line.

Pressurized condensate
header

Not pressurized

condensate header

(slope down)

F&T Trap

Pressure
gauge (optional)

Isolation Valve

Wye Strainer

CV Valve
(see table 3)

Condensate Drain
Port (see table 3)

Boiler steam
inlet port
(see table 3)

Boiler steam supply

line. Max 15 psi, Min 5 psi

measured at CV Valve

6 in.

(15 cm)

Max

Actuator

Condensate drain line.

Gravity feed to boiler.

Use pump if condensate

must be lifted.

Note: Nortec supplies CV valve, actuator
and wye strainer. All other
components and fittings by others.

Boiler steam

inlet port location

on SE 1050

Slope

dow

n only