Page 57
Operation | 54
(Control Settings Continued)
Source
Configures the humidifier to either
accept analog control signals from a
humidistat or digital signals from a
Building Management System
REG Mode
Configures the type of control used
with the humidifier. RH (P) is
proportional only internal control
based on a transducer signal. RH
(PI) is proportional control with an
integral.
MOD Mode
Configures the humidifier to either
operate with a single channel
(control only) or dual channel (control
and high limit). If an On/Off high
limit humidistat is used set MOD
Mode to Single CH
Multi Mode
Use Multi Mode to configure the
humidifier to operate as one
humidifier of a group controlled by a
single control signal / transducer
signal. See Multi Unit Op. Range
later in this section. (Default =
Standalone)
Control Setting
Source
: Analog
REG Mode
: Demand
MOD Mode
: Dual CH
Multi Mode
: Standalone
CNT Type
: 0-10
LIM Type
: 0-10
Short CD
: On
Short CD Tm
: 30 s
Time Prop.
: Off
Manual Cap
: 100%
Mulit Unit Op Range
Modbus Settings
Press Base
: On
Supply Press.
: 15 psi
RH Settings
Menu
Set
Source
Analog
Analog
Digital
Menu
Set
Source
: Analog
Analog
Only present if Mod Mode set to Dual CH
Only present if Short CD set to On
Only present if Multimode set to Master or Slave
Only present if Press Base set to On
Only present if REG Mode set to RH (P) or RH (PI)
Regulation Mode
Demand
Demand
On/Off
RH (P)
RH (PI)
Menu
Set
REG Mode
: Demand
Demand
MOD Mode
Single CH
Single CH
Dual CH
Menu
Set
MOD Mode
: Single CH
Single CH
Multi Mode
StandAlone
StandAlone
Master
Slave
Menu
Set
Multi Mode
: Standalone
Standalone