Operation | 54

(Control Settings Continued)




Source
Configures the humidifier to either
accept analog control signals from a
humidistat or digital signals from a
Building Management System

REG Mode
Configures the type of control used
with the humidifier. RH (P) is
proportional only internal control
based on a transducer signal. RH
(PI) is proportional control with an
integral.

MOD Mode
Configures the humidifier to either
operate with a single channel
(control only) or dual channel (control
and high limit). If an On/Off high
limit humidistat is used set MOD
Mode to Single CH

Multi Mode
Use Multi Mode to configure the
humidifier to operate as one
humidifier of a group controlled by a
single control signal / transducer
signal. See Multi Unit Op. Range
later in this section. (Default =
Standalone)


Control Setting
Source

: Analog

REG Mode

: Demand

MOD Mode

: Dual CH

Multi Mode

: Standalone

CNT Type

: 0-10

LIM Type

: 0-10

Short CD

: On

Short CD Tm

: 30 s

Time Prop.

: Off

Manual Cap

: 100%

Mulit Unit Op Range
Modbus Settings
Press Base

: On

Supply Press.

: 15 psi

RH Settings

Menu

Set

Source
Analog
Analog
Digital

Menu

Set

Source

: Analog

Analog

Only present if Mod Mode set to Dual CH

Only present if Short CD set to On

Only present if Multimode set to Master or Slave

Only present if Press Base set to On

Only present if REG Mode set to RH (P) or RH (PI)

Regulation Mode
Demand
Demand
On/Off
RH (P)
RH (PI)

Menu

Set

REG Mode

: Demand

Demand

MOD Mode
Single CH
Single CH
Dual CH

Menu

Set

MOD Mode

: Single CH

Single CH

Multi Mode
StandAlone
StandAlone
Master
Slave

Menu

Set

Multi Mode

: Standalone

Standalone