Nortec SE Series User Manual
Page 58
55 | Operation
(Control Settings Continued)
CNT Type
Configures the Volt or amp range of
the control signal connected to the
humidifier
LIM Type
Configures the Volt or amp range of
the high limit control signal
connected to the humidifier. The
type of control, VDC or mA, must be
the same as that of CNT Type.
Short Cycle Delay
Sets whether the humidifier must
stay off for a fixed period of time (set
by the Short CD Tim parameter)
whenever demand falls below the On
threshold to prevent short cycling.
(Defualt = Off).
Short CD Tim
Specifies the minimum time the
humidifier must remain in idle
whenever demand drops to the off
condition. It is only checked if Short
CD is set to On. (Default = 30 s)
Time Prop
Sets whether the humidifier will run
in time proportioning mode when
demand is less than 15%. On results
in the humidifier turning on and off
for short periods of time to simulate
low output. (Default = Off).
Manual Cap
Reduces the maximum capacity of
the humidifier to a percentage of its
full capacity. Use up/down buttons
to increase/decrease and press Set
to save the setting. (Default = 100%)
CNT Type
0-10 V
0-5 V
1-5 V
0-10V
2-10 V
0-16 V
32-16 V
0-20 mA
4-20 mA
Menu
Set
0-10 V
CNT Type
: 0-10
Short Cycle Delay
Off
Off
On
Menu
Set
Short CD
: Off
Off
LIM Type
: 0-10V
LIM Type
0-10 V
0-5 V
1-5 V
0-10V
2-10 V
0-16 V
3.2-16 V
Menu
Set
0-10 V
Short Cycle Delay Time
30 s
30 s
Menu
Set
Short CD Tm
: 30 s
30 s
Time Prop.
: Off
Time Proportioning
Off
Off
On
Menu
Set
Off
Manual Capacity
100%
100%
Menu
Set
Manual Cap
: 100%
100%