37 | Start Up
8 The green humidifying LED on the front of the humidifier will light up and the display will
indicated “Humidifying” and the amount of steam being produced (SETC only).
Status Screens
In addition to the main status screen the SETC includes several status screens which provide
additional information about the humidifier. The additional screens can be reached by pressing
the buttons corresponding to the left and right arrow key on the LCD display.
Main Status Screen
This screen reports the current request for humidity, status,
output, date and time, and security loop status. If status is not
idle or humidifying the left arrow key becomes a “?”. If the button
corresponding to the arrow key is pressed the display will give
additional information on the status of the humidifier.
Control Information Screen
Output is the lb/hr steam output of
the unit. Man Cap is the user
configured capacity limitation.
Depending on the control
configuration the screen also
reports the current inputs of channel
1 and 2. If the unit is configured for
internal control it also provides the
current humidity and setpoints.
Humidifier Information Screen
Model is the humidifier model type.
Capacity is maximum output if the unit is supplied 15 psi steam.
Multimode indicates if the humidifier is operating as part of a
group controlled by a single control signal
REG Mode is the configured control method.
Software is the installed software version.
Request
– xx%
Idle
0 lb/hr
04/30/09
14:25:22
Security loop:
Closed
Menu
CONTROL
Man Cap.
: 100%
Demand
: 55%
Limit
: 80%
Output
: 0 lb/hr
Menu
CONTROL
Man Cap.
: 100%
RH CNT
: 55%
CNT Set-Pt
: 50%
RH Limit
: 100%
LIM Set-Pt
: 70%
Output
: 0 lb/hr
Menu
HUMIDIFIER
Model
: SETC 750
Capacity
: 750 lb/hr
Multimode
: StandAlone
REG Mode
: Demand
Software
: XVXX
Press. In
: 15 psi
Menu
Caution:
Improper control configuration can result in over humidifying which can result in
damage to property.
See Advanced Control Configuration if the controls displayed in the control
information screen do not match those connected to the humidifier.
Request
– 100%
Idle
750 lb/hr
04/30/09
14:25:22
Security loop:
Closed